Water Vertical Deluxe - 200 to 1200 cfm -- Specifications & Dimensions
Cooling Capacities for Water Temperature Rise 10° - Entering Air 80° DB/67° WB
SIZE
ROWS
CIR.
CFM
10
3
3
1110
4
4
1055
Entering Water Temperature 42°
TOTAL BTU
SEBS BTU
GPM
WPD
APD
GPM/CIR.
TUBE VEL.
52.9
34.2
11.1
16.2
0.285
3.7
6.3
59.0
37.1
12.4
12.0
0.351
3.1
5.3
Entering Water Temperature 45°
TOTAL BTU
SEBS BTU
GPM
WPD
APD
GPM/CIR.
TUBE VEL.
40.7
28.8
8.5
10.2
0.272
2.8
4.8
46.0
31.4
9.6
7.9
0.336
2.4
4.1
Vertical Deluxe 200 - 1200 cfm
Model VDSW
A
B
C
D
E
F
G
H
J
K
L
M
FILTER
10
57 3/4
13 5/8
8 1/2
14 1/8
10
12
26
30
9 3/8
11 7/8
11 7/8
63 3/8
11x38x1
Vertical Deluxe Models 02 thru 12
Right-hand unit shown, left hand unit opposite.
Coil connections determined by facing the supply-air opening.
Electrical junction box is located on the same side as the coil connections.
Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT primary and secondary drain connections.
Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
Coil connections: 1/2" CW on model 02-06. 3/4" on 08-12 and 1/2" HW on 02-12.
Coil Company, LLC
3223 Phoenixville Pike
Malvern, PA 19355
800.523.7590 [toll free]
610.251.0257 [local]
610.251.0805 [fax]
Home
|
Contact Us
|
Site Guide
|
HVAC Coils - Replacement or New
|
Space Coolers
Quickaire Fan Coil Units
|
Stock Hot Water Booster Coils
|
Quickaire Belt Drive Air Handlers
|
Newsletters