Water Vertical Deluxe - 200 to 1200 cfm -- Specifications & Dimensions
Cooling Capacities for Water Temperature Rise 10° - Entering Air 80° DB/67° WB
SIZE
ROWS
CIR.
CFM
08
3
3
900
4
4
860
Entering Water Temperature 42°
TOTAL BTU
SEBS BTU
GPM
WPD
APD
GPM/CIR.
TUBE VEL.
43.6
28.0
9.2
11.1
0.244
3.1
5.2
48.6
30.5
10.2
8.4
0.303
2.6
4.3
Entering Water Temperature 45°
TOTAL BTU
SEBS BTU
GPM
WPD
APD
GPM/CIR.
TUBE VEL.
33.5
23.7
7.0
6.7
0.233
2.3
4.0
37.8
25.9
7.9
5.2
0.290
2.0
3.4
Vertical Deluxe 200 - 1200 cfm
Model VDSW
A
B
C
D
E
F
G
H
J
K
L
M
FILTER
08
57 3/4
13 5/8
8 1/2
18 1/8
10
12
26
30
13 3/8
11 7/8
11 7/8
63 3/8
11x34x1
Vertical Deluxe Models 02 thru 12
Right-hand unit shown, left hand unit opposite.
Coil connections determined by facing the supply-air opening.
Electrical junction box is located on the same side as the coil connections.
Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT primary and secondary drain connections.
Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
Coil connections: 1/2" CW on model 02-06. 3/4" on 08-12 and 1/2" HW on 02-12.
Coil Company, LLC
3223 Phoenixville Pike
Malvern, PA 19355
800.523.7590 [toll free]
610.251.0257 [local]
610.251.0805 [fax]
Home
|
Contact Us
|
Site Guide
|
HVAC Coils - Replacement or New
|
Space Coolers
Quickaire Fan Coil Units
|
Stock Hot Water Booster Coils
|
Quickaire Belt Drive Air Handlers
|
Newsletters