Water Vertical Deluxe - 200 to 1200 cfm -- Specifications & Dimensions


Water Vertical Deluxe - 200 to 1200 cfm -- Specifications & Dimensions

Cooling Capacities for Water Temperature Rise 10° - Entering Air 80° DB/67° WB
SIZE ROWS
CIR.

CFM
06 3 2 705
4 2 665
Entering Water Temperature 42°
TOTAL BTU SEBS BTU GPM WPD APD GPM/CIR. TUBE VEL.
34.7 22.2 7.3 17.1 0.248 3.6 6.2
39.3 24.3 8.2 27.9 0.301 4.1 7.0
Entering Water Temperature 45°
TOTAL BTU SEBS BTU GPM WPD APD GPM/CIR. TUBE VEL.
27.0 19.0 5.7 10.9 0.238 2.9 4.9
31.2 20.7 6.6 18.5 0.293 3.3 5.6

Vertical Deluxe 200 - 1200 cfm
Model VDSW
A
B
C
D
E
F
G
H J K L M FILTER
06
52 1/8
11 3/8
7
13 1/4
8
11 1/4
22
26 8 3/4 10 10 1/2 57 3/4 10x36x1

Vertical Deluxe Models 02 thru 12

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 1/2" CW on model 02-06. 3/4" on 08-12 and 1/2" HW on 02-12.
 

Coil Company, LLC
3223 Phoenixville Pike
Malvern, PA 19355

800.523.7590 [toll free]
610.251.0257 [local]
610.251.0805 [fax]