Water Vertical Deluxe - 200 to 1200 cfm -- Specifications & Dimensions
Cooling Capacities for Water Temperature Rise 10° - Entering Air 80° DB/67° WB
SIZE
ROWS
CIR.
CFM
06
3
2
705
4
2
665
Entering Water Temperature 42°
TOTAL BTU
SEBS BTU
GPM
WPD
APD
GPM/CIR.
TUBE VEL.
34.7
22.2
7.3
17.1
0.248
3.6
6.2
39.3
24.3
8.2
27.9
0.301
4.1
7.0
Entering Water Temperature 45°
TOTAL BTU
SEBS BTU
GPM
WPD
APD
GPM/CIR.
TUBE VEL.
27.0
19.0
5.7
10.9
0.238
2.9
4.9
31.2
20.7
6.6
18.5
0.293
3.3
5.6
Vertical Deluxe 200 - 1200 cfm
Model VDSW
A
B
C
D
E
F
G
H
J
K
L
M
FILTER
06
52 1/8
11 3/8
7
13 1/4
8
11 1/4
22
26
8 3/4
10
10 1/2
57 3/4
10x36x1
Vertical Deluxe Models 02 thru 12
Right-hand unit shown, left hand unit opposite.
Coil connections determined by facing the supply-air opening.
Electrical junction box is located on the same side as the coil connections.
Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT primary and secondary drain connections.
Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
Coil connections: 1/2" CW on model 02-06. 3/4" on 08-12 and 1/2" HW on 02-12.
Coil Company, LLC
3223 Phoenixville Pike
Malvern, PA 19355
800.523.7590 [toll free]
610.251.0257 [local]
610.251.0805 [fax]