DX COOLING CAPACITIES - ENTERING AIR 80°F DB/67°F WB
SIZE ROWS
CIR.

CFM
12 3 4 1275
4 5 1210
Suction Temperature 42°
TOTAL BTU SENS BTU
LDB
LWB
APD
51.8 35.2 54.7 54.0 0.304
58.9 38.6 50.9 50.9 0.373
Suction Temperature 45°
TOTAL BTU SENS BTU
LDB
LWB
APD
44.9 32.4 56.7 55.9 55.9
51.1 35.5 53.2 53.2 0.373

Vertical Basic 200 - 1200 cfm
Model VBSX
A
B
C
D
E
F
G
H J K FILTER
12
45
41
10 1/4
3
42
25 1/2
1/4
5 1/2 11 11 11x42x1

Vertical Basic Models 02 thru 12

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 1/2" CW on model 02-06. 3/4" on 08-12 and 1/2" HW on 02-12.