DX Vertical Basic - 200 to 1200 cfm -- Specifications & Dimensions


DX Vertical Basic - 200 to 1200 cfm -- Specifications & Dimensions

DX COOLING CAPACITIES - ENTERING AIR 80°F DB/67°F WB
SIZE ROWS
CIR.

CFM
08 3 3 900
4 4 860
Suction Temperature 42°
TOTAL BTU SENS BTU
LDB
LWB
APD
38.9 26.1 53.4 53.0 0.245
43.5 28.6 49.6 49.6 0.304
Suction Temperature 45°
TOTAL BTU SENS BTU
LDB
LWB
APD
33.9 24.1 55.5 55.0 0.245
37.9 25.8 52.6 52.6 0.304

Vertical Basic 200 - 1200 cfm
Model VBSX
A
B
C
D
E
F
G
H J K FILTER
08
37
33
10 1/4
3
34
25 1/2
1/4
5 1/2 11 11 11x34x1

Vertical Basic Models 02 thru 12

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 1/2" CW on model 02-06. 3/4" on 08-12 and 1/2" HW on 02-12.

Coil Company, LLC
3223 Phoenixville Pike
Malvern, PA 19355

800.523.7590 [toll free]
610.251.0257 [local]
610.251.0805 [fax]