Water Vertical Low-Silhouette Deluxe - 400 to 600 cfm - Specifications & Dimensions
Cooling Capacities for Water Temperature Rise 10° - Entering Air 80° DB/67° WB
LDSW
SIZE
ROWS
CIR.
CFM
06
2
2
715
3
2
665
Entering Water Temperature 42°
TOTAL BTU
SEBS BTU
GPM
WPD
APD
GPM/CIR.
TUBE VEL.
24.1
16.6
5.1
6.2
0.196
2.5
4.3
31.9
20.5
6.7
14.1
0.262
3.4
5.7
Entering Water Temperature 45°
TOTAL BTU
SEBS BTU
GPM
WPD
APD
GPM/CIR.
TUBE VEL.
15.0
15.0
3.2
2.6
0.133
1.6
2.7
24.6
17.5
5.2
9.0
0.250
2.6
4.4
Vertical Low-Silhouette Models 04 and 06
Right-hand unit shown, left hand unit opposite.
Coil connections determined by facing the supply-air opening.
Electrical junction box is located on the same side as the coil connections.
Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT primary and secondary drain connections.
Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
Coil connections: 1/2" CW on model 04-06