Water Vertical Low-Silhouette Basic - 400 to 600 cfm - Specifications & Dimensions


Water Vertical Low-Silhouette Basic - 400 to 600 cfm - Specifications & Dimensions

Cooling Capacities for Water Temperature Rise 10° - Entering Air 80° DB/67° WB
LBSW
SIZE
ROWS
CIR.

CFM
04 2 2 470
3 2 450
Entering Water Temperature 42°
TOTAL BTU SEBS BTU GPM WPD APD GPM/CIR. TUBE VEL.
18.8 12.4 4.0 4.0 0.100 2.0 3.3
24.4 15.3 5.2 9.1 0.139 2.6 4.4
Entering Water Temperature 45°
TOTAL BTU SEBS BTU GPM WPD APD GPM/CIR. TUBE VEL.
14.1 10.6 3.0 2.3 0.094 1.5 2.5
18.9 13.0 4.0 5.7 0.135 2.0 3.4


Vertical Low-Silhouette Models 04 and 06

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 1/2" CW on model 04-06

Coil Company, LLC
3223 Phoenixville Pike
Malvern, PA 19355

800.523.7590 [toll free]
610.251.0257 [local]
610.251.0805 [fax]