DX Horizontal Return Plenum - Rear Return - 200 to 1200 cfm -- Specifications & Dimensions


DX Horizontal Return Plenum - Rear Return - 200 to 1200 cfm -- Specifications & Dimensions

DX COOLING CAPACITIES - ENTERING AIR 80°F DB/67°F WB
SIZE ROWS
CIR.

CFM
06 3 3 780
4 4 710
Suction Temperature 42°
TOTAL BTU SENS BTU
LDB
LWB
APD
23.7 17.7 59.3 57.6 0.528
27.0 19.1 55.4 54.9 0.608
Suction Temperature 45°
TOTAL BTU SENS BTU
LDB
LWB
APD
19.7 15.8 61.5 59.3 0.528
22.6 17.6 57.3 57.1 0.606

Horizontal Return Plenum - Rear Return
Model HRSXR
A
B
C
D
E
F
G
H FILTER SIZE
06
54
25 7/8
11
39 3/8
55 3/8
52 1/4
37 1/8
12 12X25


Model 04 to 12

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 1/2" CW on siezes 04 & 06, 3/4" on sizes 08-12 and 1/2" HW on sizes 04-12.

Coil Company, LLC
3223 Phoenixville Pike
Malvern, PA 19355

800.523.7590 [toll free]
610.251.0257 [local]