Water Horizontal Return Plenum - Bottom Return - 200 to 1200 cfm -- Specifications & Dimensions


Water Horizontal Return Plenum - Bottom Return - 200 to 1200 cfm -- Specifications & Dimensions

Cooling Capacities for Water Temperature Rise 10° - Entering Air 80° DB/67° WB
SIZE ROWS
CIR.

CFM
12 3 3 1370
4 4 1290
Entering Water Temperature 42°
TOTAL BTU SEBS BTU GPM WPD APD GPM/CIR. TUBE VEL.
52.5 35.7 11.1 12.3 0.585 3.7 6.3
60.4 39.7 12.7 9.6 0.708 3.2 5.4
Entering Water Temperature 45°
TOTAL BTU SEBS BTU GPM WPD APD GPM/CIR. TUBE VEL.
39.8 30.8 8.4 7.6 0.539 2.8 4.7
46.3 33.9 9.7 6.2 0.663 2.4 4.1

Horizontal Bottom Return - Air Plenum
Model HRSWB
A
B
C
D
E
F
G
H J K L M N FILTER SIZE
12
49 1/2
44 7/8
43
6
44
46
47 3/16
10 3/8 7 13/16 26 1/2 10 12 1/4 13 1/4 12x46x1


Model 04 to 12

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 1/2" CW on siezes 04 & 06, 3/4" on sizes 08-12 and 1/2" HW on sizes 04-12.

Coil Company, LLC
3223 Phoenixville Pike
Malvern, PA 19355

800.523.7590 [toll free]
610.251.0257 [local]
610.251.0805 [fax]