DX Horizontal Return Plenum - Rear Return
High Performance - 600 to 2200 cfm -- Specifications &
Dimensions

|
DX
COOLING CAPACITIES - ENTERING AIR 80°F DB/67°F
WB
|
| SIZE |
ROWS |
CIR. |
CFM |
| 18 |
3 |
5 |
2005 |
| 4 |
10 |
2005 |
| 6 |
10 |
2005 |
|
|
Suction
Temperature 42°
|
| TOTAL
BTU |
SENS
BTU |
LDB |
LWB |
APD |
| 63.7 |
45.4 |
59.3 |
57.1 |
0.613 |
| 68.8 |
51.1 |
56.7 |
56.2 |
0.818 |
| 96.0 |
65.3 |
50.2 |
50.2 |
1.227 |
|
|
Suction
Temperature 45°
|
| TOTAL
BTU |
SENS
BTU |
LDB |
LWB |
APD |
| 54.3 |
41.9 |
60.9 |
58.7 |
0.613 |
| 54.3 |
41.9 |
60.9 |
58.7 |
0.613 |
| 57.0 |
45.8 |
59.1 |
58.3 |
0.798 |
|
|
Horizontal
Rear Return - Air Plenum - High Performance 600-2200
cfm
|
|
Model
HRHXR
|
A
|
B
|
C
|
D |
E |
F |
Filter
Size |
|
18
|
49
1/2
|
43
|
44
3/4
|
44
1/16 |
46
1/8 |
47
3/16 |
17x46x1 |
|
|
Horizontal
Rear Return - Air Plenum High Performance Models
15 to 22
- Right-hand
unit shown, left hand unit opposite.
- Coil
connections determined by facing the supply-air
opening.
- Electrical
junction box is located on the same side as the
coil connections.
- Drain
pan is powder-coated epoxy with 1/4" thick
closed-cell insulation and has 3/4" NPT primary
and secondary drain connections.
- Entire
cabinet, scroll and blower wheel are heavy-gauge,
galvanized steel.
- Coil
connections: 3/4" CW on sizes 15-22 and 1/2"
HW on sizes 15-22
|
|
|
 |
 |
 |

| |
Coil Company, LLC
3223 Phoenixville Pike
Malvern, PA 19355 |
800.523.7590 [toll free]
610.251.0257 [local]
610.251.0805 [fax] |
 |
|
|
Home
| Contact
Us | Site
Guide | HVAC
Coils - Replacement or New | Space
Coolers
Quickaire
Fan Coil Units | Stock
Hot Water Booster Coils | Quickaire
Belt Drive Air Handlers | Newsletters
|
|