prod lit
Coil Selection Download
 


DX Horizontal Bottom Return Air-Plenum - High Performance - 600 to 2200 cfm - Specifications & Dimensions


DX Horizontal Bottom Return Air-Plenum - High Performance - 600 to 2200 cfm - Specifications & Dimensions

DX COOLING CAPACITIES - ENTERING AIR 80°F DB/67°F WB
SIZE ROWS
CIR.

CFM
18 3 5 2005
4 10 2005
6 10 2005
Suction Temperature 42°
TOTAL BTU SENS BTU
LDB
LWB
APD
63.7 45.4 59.3 57.1 0.613
68.8 51.1 56.7 56.2 0.818
96.0 65.3 50.2 50.2 1.227
Suction Temperature 45°
TOTAL BTU SENS BTU
LDB
LWB
APD
54.3 41.9 60.9 58.7 0.613
54.3 41.9 60.9 58.7 0.613
57.0 45.8 59.1 58.3 0.798

Horizontal Bottom Return - Air Plenum - High Performance
600-2200 cfm
Model HRHXB
A
B
C
D E F Filter Size
18
49 1/2
43
44 3/4
44 1/16 46 1/8 47 3/16 17x46x1


Horizontal Bottom Return - Air Plenum High Performance Models 15 to 22

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 3/4" CW on sizes 15-22 and 1/2" HW on sizes 15-22

Coil Company, LLC
3223 Phoenixville Pike
Malvern, PA 19355

800.523.7590 [toll free]
610.251.0257 [local]
610.251.0805 [fax]