DX Horizontal Bottom Return Air-Plenum - High Performance - 600 to 2200 cfm - Specifications & Dimensions


DX Horizontal Bottom Return Air-Plenum - High Performance - 600 to 2200 cfm - Specifications & Dimensions

DX COOLING CAPACITIES - ENTERING AIR 80°F DB/67°F WB
SIZE ROWS
CIR.

CFM
10 3 3 1145
4 4 1140
6 6 1050
Suction Temperature 42°
TOTAL BTU SENS BTU
LDB
LWB
APD
35.8 25.9 59.3 57.3 0.613
43.4 30.7 55.4 54.9 0.811
51.4 34.2 50.2 50.2 1.071
Suction Temperature 45°
TOTAL BTU SENS BTU
LDB
LWB
APD
30.5 23.9 60.9 58.9 0.613
37.0 28.3 57.3 56.9 0.811
44.1 31.5 52.6 52.6 1.071

Horizontal Bottom Return - Air Plenum - High Performance
600-2200 cfm
Model HRHXB
A
B
C
D E F Filter Size
10
31 1/2
25
26
26 1/16 29 3/16 29 3/8 17x28x1


Horizontal Bottom Return - Air Plenum High Performance Models 06 to 12

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 1/2" CW on size 06, 3/4" on sizes 08-12 and 1/2" HW on sizes 06 - 12