DX COOLING CAPACITIES - ENTERING AIR 80°F DB/67°F WB
SIZE ROWS
CIR.

CFM
08 3 3 855
4 4 855
6 6 850
Suction Temperature 42°
TOTAL BTU SENS BTU
LDB
LWB
APD
24.7 18.8 59.9 58.1 0.609
30.0 21.8 56.7 55.9 0.811
37.7 25.9 52.1 52.1 1.206
Suction Temperature 45°
TOTAL BTU SENS BTU
LDB
LWB
APD
20.6 16.7 62.1 59.7 0.607
25.1 20.1 58.5 58.0 0.801
31.7 23.8 54.3 54.3 1.180

Horizontal Bottom Return - Air Plenum - High Performance
600-2200 cfm
Model HRHXB
A
B
C
D E F Filter Size
08
25 1/2
19
20
20 1/16 23 3/16 23 3/8 17x22x1


Horizontal Bottom Return - Air Plenum High Performance Models 06 to 12

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 1/2" CW on size 06, 3/4" on sizes 08-12 and 1/2" HW on sizes 06 - 12