Water Horizontal Rear Return Plenum - High Performance - 600 to 2200 cfm - Specifications & Dimensions


Water Horizontal Return Plenum - Rear Return - High Performance - 600 to 2200 cfm -- Specifications & Dimensions

Cooling Capacities for Water Temperature Rise 10° - Entering Air 80° DB/67° WB
SIZE ROWS
CIR.

CFM
18 3 5 2005
4 10 2005
Entering Water Temperature 42°
TOTAL BTU SEBS BTU GPM WPD APD GPM/CIR. TUBE VEL.
73.9 50.8 15.6 8.4 0.602 3.1 5.3
79.6 55.9 16.8 2.6 0.777 1.7 2.9
Entering Water Temperature 45°
TOTAL BTU SEBS BTU GPM WPD APD GPM/CIR. TUBE VEL.
55.7 43.8 11.7 4.9 0.552 2.3 4.0
60.1 48.3 12.7 1.5 0.719 1.3 2.1

Horizontal Rear Return - Air Plenum - High Performance 600-2200 cfm
Model HRHWR
A
B
C
D E F Filter Size
18
49 1/2
43
44 3/4
44 1/16 46 1/8 47 3/16 17x46x1


Horizontal Rear Return - Air Plenum High Performance Models 15 to 22

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 3/4" CW on sizes 15-22 and 1/2" HW on sizes 15-22

Coil Company, LLC
3223 Phoenixville Pike
Malvern, PA 19355

800.523.7590 [toll free]
610.251.0257 [local]