Water Horizontal Rear Return Plenum - High Performance - 600 to 2200 cfm - Specifications & Dimensions


Water Horizontal Rear Return Plenum - High Performance - 600 to 2200 cfm - Specifications & Dimensions

Cooling Capacities for Water Temperature Rise 10° - Entering Air 80° DB/67° WB
SIZE ROWS
CIR.

CFM
10 3 3 1145
4 4 1140
Entering Water Temperature 42°
TOTAL BTU SEBS BTU GPM WPD APD GPM/CIR. TUBE VEL.
41.7 29.0 8.0 8.7 0.599 2.9 5.0
49.6 33.4 10.4 7.3 0.789 2.6 4.4
Entering Water Temperature 45°
TOTAL BTU SEBS BTU GPM WPD APD GPM/CIR. TUBE VEL.
31.5 25.0 6.6 5.1 0.550 2.2 3.8
38.1 28.9 8.1 4.5 0.737 2.0 3.4

Horizontal Rear Return - Air Plenum - High Performance 600-2200 cfm
Model HRHWR
A
B
C
D E F Filter Size
10
31 1/2
25
26
26 1/16 29 3/16 29 3/8 17x28x1


Horizontal Rear Return - Air Plenum High Performance Models 06 to 12

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 1/2" CW on size 06, 3/4" on sizes 08-12 and 1/2" HW on sizes 06 - 12

Coil Company, LLC
3223 Phoenixville Pike
Malvern, PA 19355

800.523.7590 [toll free]
610.251.0257 [local]
610.251.0805 [fax]