Cooling Capacities for Water Temperature Rise 10° - Entering Air 80° DB/67° WB
SIZE ROWS
CIR.

CFM
12 3 5 1385
4 10 1350
Entering Water Temperature 42°
TOTAL BTU SEBS BTU GPM WPD APD GPM/CIR. TUBE VEL.
47.0 33.6 9.9 3.5 0.556 2.0 3.4
48.5 35.7 10.2 1.4 0.688 1.0 1.7
Entering Water Temperature 45°
TOTAL BTU SEBS BTU GPM WPD APD GPM/CIR. TUBE VEL.
31.0 31.0 6.6 1.6 0.393 1.3 2.2
36.7 31.2 7.8 0.8 0.633 0.8 1.3

Horizontal Bottom Return - Air Plenum - High Performance
600-2200 cfm
Model HRHWB
A
B
C
D E F Filter Size
37 1/2
31
32
32 1/16 35 3/16 35 3/8 17x34x1


Horizontal Bottom Return - Air Plenum High Performance Models 06 to 12

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 1/2" CW on size 06, 3/4" on sizes 08-12 and 1/2" HW on sizes 06 - 12

Coil Company, LLC
3223 Phoenixville Pike
Malvern, PA 19355

800.523.7590 [toll free]
610.251.0257 [local]