Water Horizontal Bottom Return Air-Plenum - High Performance - 600 to 2200 cfm - Specifications & Dimensions


Water Horizontal Bottom Return Air-Plenum - High Performance - 600 to 2200 cfm - Specifications & Dimensions

Cooling Capacities for Water Temperature Rise 10° - Entering Air 80° DB/67° WB
SIZE ROWS
CIR.

CFM
06 3 3 665
4 4 665
Entering Water Temperature 42°
TOTAL BTU SEBS BTU GPM WPD APD GPM/CIR. TUBE VEL.
20.6 15.4 4.4 2.3 0.567 1.5 2.5
24.8 17.8 5.2 2.1 0.758 1.3 2.2
Entering Water Temperature 45°
TOTAL BTU SEBS BTU GPM WPD APD GPM/CIR. TUBE VEL.
14.1 14.1 3.0 1.1 0.411 1.0 1.7
18.8 15.6 4.0 1.3 0.700 1.0 1.7

Horizontal Bottom Return - Air Plenum - High Performance
600-2200 cfm
Model HRHWB
A
B
C
D E F Filter Size
06
21 1/2
15
16
16 1/16 19 3/16 19 3/8 17x18x1


Horizontal Bottom Return - Air Plenum High Performance Models 06 to 12

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 1/2" CW on size 06, 3/4" on sizes 08-12 and 1/2" HW on sizes 06 - 12

Coil Company, LLC
3223 Phoenixville Pike
Malvern, PA 19355

800.523.7590 [toll free]
610.251.0257 [local]
610.251.0805 [fax]