DX Horizontal Flush - 200 to 1200 cfm -- Specifications
& Dimensions
|
DX
COOLING CAPACITIES - ENTERING AIR 80°F DB/67°F
WB
|
| SIZE |
ROWS |
CIR. |
CFM |
| 04 |
3 |
2 |
435 |
| 4 |
4 |
425 |
|
|
Suction
Temperature 42°
|
| TOTAL
BTU |
SENS
BTU |
LDB |
LWB |
APD |
| 16.5 |
11.4 |
56.0 |
55.0 |
0.301 |
| 16.7 |
12.0 |
54.1 |
54.1 |
0.387 |
|
|
Suction
Temperature 45°
|
| TOTAL
BTU |
SENS
BTU |
LDB |
LWB |
APD |
| 14.0 |
10.5 |
57.9 |
57.0 |
0.301 |
| 13.8 |
10.8 |
56.7 |
56.7 |
0.377 |
|
|
Horizontal
Flush 400 thru 1200 cfm
|
|
Model
HFSX
|
A
|
B
|
C
|
D
|
E
|
F
|
G
|
H |
J |
FILTER
SIZE |
|
04
|
46
|
25
7/8
|
11
|
6
3/8
|
25
1/8
|
27
3/4
|
47
1/2
|
44
3/8 |
25
1/8 |
(2)
12x20 |
|
|
Model
04 to 12
- Right-hand
unit shown, left hand unit opposite.
- Coil
connections determined by facing the supply-air
opening.
- Electrical
junction box is located on the same side as the
coil connections.
- Drain
pan is powder-coated epoxy with 1/4" thick
closed-cell insulation and has 3/4" NPT primary
and secondary drain connections.
- Entire
cabinet, scroll and blower wheel are heavy-gauge,
galvanized steel.
- Coil
connections: 1/2" CW on siezes 04 & 06,
3/4" on sizes 08-12 and 1/2" HW on sizes
04-12.
|
|
|
 |
|
| Coil Company, LLC
3223 Phoenixville Pike
Malvern, PA 19355 |
800.523.7590 [toll free]
610.251.0257 [local]
610.251.0805 [fax] |
|
|
|
|
| |
|
|