DX Horizontal Flush - 200 to 1200 cfm -- Specifications
& Dimensions
|
DX
COOLING CAPACITIES - ENTERING AIR 80°F DB/67°F
WB
|
| SIZE |
ROWS |
CIR. |
CFM |
| 03 |
3 |
2 |
365 |
| 4 |
4 |
340 |
|
|
Suction
Temperature 42°
|
| TOTAL
BTU |
SENS
BTU |
LDB |
LWB |
APD |
| 12.0 |
8.0 |
58.0 |
56.7 |
0.357 |
| 11.3 |
8.7 |
56.7 |
56.6 |
0.419 |
|
|
Suction
Temperature 45°
|
| TOTAL
BTU |
SENS
BTU |
LDB |
LWB |
APD |
| 10.0 |
8.1 |
59.7 |
58.6 |
0.356 |
| 9.2 |
8.0 |
59.5 |
58.5 |
0.392 |
|
|
Dimensions
- Horizontal Deluxe
|
|
Model
HFSX
|
A
|
B
|
C
|
D
|
E
|
F
|
G
|
H |
FILTER
SIZE |
|
03
|
46
|
25
7/8
|
11
|
39
3/8
|
47
3/8
|
44
1/4
|
37
1/8
|
12 |
12x20x1 |
|
|
Model
02 & 03
- Right-hand
unit shown, left hand unit opposite.
- Coil
connections determined by facing the supply-air
opening.
- Electrical
junction box is located on the same side as the
coil connections.
- Drain
pan is powder-coated epoxy with 1/4" thick
closed-cell insulation and has 3/4" NPT primary
and secondary drain connections.
- Entire
cabinet, scroll and blower wheel are heavy-gauge,
galvanized steel.
- Coil
connections: 1/2" CW and HW on sizes 02 &
03.
|
|
|
 |
 |
 |

| |
Coil Company, LLC
3223 Phoenixville Pike
Malvern, PA 19355 |
800.523.7590 [toll free]
610.251.0257 [local]
610.251.0805 [fax] |
 |
|
|
Home
| Contact
Us | Site
Guide | HVAC
Coils - Replacement or New | Space
Coolers
Quickaire
Fan Coil Units | Stock
Hot Water Booster Coils | Quickaire
Belt Drive Air Handlers | Newsletters
|
|