Water Horizontal Flush - 200 to 1200 cfm -- Specifications & Dimensions


Water Horizontal Flush - 200 to 1200 cfm -- Specifications & Dimensions

Cooling Capacities for Water Temperature Rise 10° - Entering Air 80° DB/67° WB
SIZE ROWS
CIR.

CFM
10 3 3 1140
4 4 1080
Entering Water Temperature 42°
TOTAL BTU SEBS BTU GPM WPD APD GPM/CIR. TUBE VEL.
42.9 29.3 9.1 8.2 0.554 3.0 5.1
49.5 32.9 10.5 6.7 0.678 2.6 4.4
Entering Water Temperature 45°
TOTAL BTU SEBS BTU GPM WPD APD GPM/CIR. TUBE VEL.
32.4 25.3 6.8 4.8 0.510 2.3 3.9
37.8 28.1 8.0 4.0 0.634 2.0 3.4

Horizontal Flush 400 thru 1200 cfm
Model HFSW
A
B
C
D
E
F
G
H J FILTER SIZE
10
60
25 7/8
12
6 3/8
37 1/8
27 3/4
61 1/2
58 3/8 25 1/8 (2) 12x25


Model 04 to 12

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 1/2" CW on siezes 04 & 06, 3/4" on sizes 08-12 and 1/2" HW on sizes 04-12.

Coil Company, LLC
3223 Phoenixville Pike
Malvern, PA 19355

800.523.7590 [toll free]
610.251.0257 [local]
610.251.0805 [fax]