DX Horizontal Flush - High Performance - 600 to 2200 cfm
-- Specifications & Dimensions
|
DX
COOLING CAPACITIES - ENTERING AIR 80°F DB/67°F
WB
|
| SIZE |
ROWS |
CIR. |
CFM |
| 10 |
3 |
3 |
1145 |
| 4 |
4 |
1140 |
| 6 |
6 |
1050 |
|
|
Suction
Temperature 42°
|
| TOTAL
BTU |
SENS
BTU |
LDB |
LWB |
APD |
| 35.8 |
25.9 |
59.3 |
57.3 |
0.613 |
| 43.4 |
30.7 |
55.4 |
54.9 |
0.811 |
| 51.4 |
34.2 |
50.2 |
50.2 |
1.071 |
|
|
Suction
Temperature 45°
|
| TOTAL
BTU |
SENS
BTU |
LDB |
LWB |
APD |
| 30.5 |
23.9 |
60.9 |
58.9 |
0.613 |
| 37.0 |
28.3 |
57.3 |
56.9 |
0.811 |
| 44.1 |
31.5 |
52.6 |
52.6 |
1.071 |
|
|
Horizontal
Flush - High Performance - 600-2200 cfm
|
|
Model
HFHX
|
A
|
B
|
C
|
D |
Filter Size |
|
10
|
25
5/16
|
44
3/8
|
46
|
47
1/2 |
(2)
12x20x1 |
|
|
Horizontal
Flush - High Performance Models 06 thru 12
- Right-hand
unit shown, left hand unit opposite.
- Coil
connections determined by facing the supply-air
opening.
- Electrical
junction box is located on the same side as the
coil connections.
- Drain
pan is powder-coated epoxy with 1/4" thick
closed-cell insulation and has 3/4" NPT primary
and secondary drain connections.
- Entire
cabinet, scroll and blower wheel are heavy-gauge,
galvanized steel.
- Coil
connections: 1/2" CW on size 06, 3/4"
on sizes 08-12 and 1/2" HW on sizes 06-12
|
|
|
 |
|
| Coil Company, LLC
3223 Phoenixville Pike
Malvern, PA 19355 |
800.523.7590 [toll free]
610.251.0257 [local]
610.251.0805 [fax] |
|
|
|
|
| |
|
|