Water Horizontal Flush - High Performance - 600 to 2200
cfm -- Specifications & Dimensions
|
Cooling
Capacities for Water Temperature Rise 10° -
Entering Air 80° DB/67° WB
|
| SIZE |
ROWS |
CIR. |
CFM |
| 18 |
3 |
5 |
2005 |
| 4 |
10 |
2005 |
|
|
Entering
Water Temperature 42°
|
| TOTAL
BTU |
SEBS
BTU |
GPM |
WPD |
APD |
GPM/CIR. |
TUBE
VEL. |
| 73.9 |
50.8 |
15.6 |
8.4 |
0.602 |
3.1 |
5.3 |
| 79.6 |
55.9 |
16.8 |
2.6 |
0.777 |
1.7 |
2.9 |
|
|
Entering
Water Temperature 45°
|
| TOTAL
BTU |
SEBS
BTU |
GPM |
WPD |
APD |
GPM/CIR. |
TUBE
VEL. |
| 55.7 |
43.8 |
11.7 |
4.9 |
0.552 |
2.3 |
4.0 |
| 60.1 |
48.3 |
12.7 |
1.5 |
0.719 |
1.3 |
2.1 |
|
|
Horizontal
Flush - High Performance - 600-2200 cfm
|
|
Model
HFHW
|
A
|
B
|
C
|
D |
Filter Size |
|
18
|
43
5/16
|
58
3/8
|
60
|
61
1/2 |
(3)
12x20x1 |
|
|
Horizontal
Flush - High Performance Models 06 thru 12
- Right-hand
unit shown, left hand unit opposite.
- Coil
connections determined by facing the supply-air
opening.
- Electrical
junction box is located on the same side as the
coil connections.
- Drain
pan is powder-coated epoxy with 1/4" thick
closed-cell insulation and has 3/4" NPT primary
and secondary drain connections.
- Entire
cabinet, scroll and blower wheel are heavy-gauge,
galvanized steel.
- Coil
connections: 3/4" CW on sizes 15-22 and 1/2"
HW on sizes 15-22
|
|
|
 |
 |
 |

| |
Coil Company, LLC
3223 Phoenixville Pike
Malvern, PA 19355 |
800.523.7590 [toll free]
610.251.0257 [local]
610.251.0805 [fax] |
 |
|
|
Home
| Contact
Us | Site
Guide | HVAC
Coils - Replacement or New | Space
Coolers
Quickaire
Fan Coil Units | Stock
Hot Water Booster Coils | Quickaire
Belt Drive Air Handlers | Newsletters
|
|