DX Horizontal Deluxe - 200 to 1200 cfm -- Specifications & Dimensions


DX Horizontal Deluxe - 200 to 1200 cfm -- Specifications & Dimensions

DX COOLING CAPACITIES - ENTERING AIR 80°F DB/67°F WB
SIZE ROWS
CIR.

CFM
12 3 3 1370
4 4 1290
Suction Temperature 42°
TOTAL BTU SENS BTU
LDB
LWB
APD
45.2 32.0 58.6 56.7 0.591
52.6 36.5 54.1 54.9 0.717
Suction Temperature 45°
TOTAL BTU SENS BTU
LDB
LWB
APD
38.8 29.5 60.3 58.3 0.591
45.4 33.7 56.1 55.9 0.717

Dimensions - Horizontal Deluxe
Model HDSW
A
B
C
D
E
F
G
H FILTER SIZE
12
12 3/8
61
28
25
58
9 3/8
7 3/4
42 1/4 (2) 12x25


Model 04 thru 12

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 1/2" CW on sizes 04 & 06, 3/4" on sizes 08-12 and 1/2" HW on sizes 04-12.