DX Horizontal Deluxe - 200 to 1200 cfm -- Specifications & Dimensions


DX Horizontal Deluxe - 200 to 1200 cfm -- Specifications & Dimensions

DX COOLING CAPACITIES - ENTERING AIR 80°F DB/67°F WB
SIZE ROWS
CIR.

CFM
03 3 2 365
4 4 340
Suction Temperature 42°
TOTAL BTU SENS BTU
LDB
LWB
APD
12.0 8.0 58.0 56.7 0.357
11.3 8.7 56.7 56.6 0.419
Suction Temperature 45°
TOTAL BTU SENS BTU
LDB
LWB
APD
10.0 8.1 59.7 58.6 0.356
9.2 8.0 59.5 58.5 0.392


Model 02 & 03

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 1/2" CW and HW on models 02 & 03.

Coil Company, LLC
3223 Phoenixville Pike
Malvern, PA 19355

800.523.7590 [toll free]
610.251.0257 [local]
610.251.0805 [fax]