DX Horizontal Deluxe - High Performance - 600 to 2200 cfm -- Specifications & Dimensions


DX Horizontal Deluxe - High Performance - 600 to 2200 cfm -- Specifications & Dimensions

DX COOLING CAPACITIES - ENTERING AIR 80°F DB/67°F WB
SIZE ROWS
CIR.

CFM
22 3 5 2005
4 10 2005
6 10 2005
Suction Temperature 42°
TOTAL BTU SENS BTU
LDB
LWB
APD
63.7 45.4 59.3 57.1 0.613
68.8 51.1 56.7 56.2 0.818
96.0 65.3 50.2 50.2 1.227
Suction Temperature 45°
TOTAL BTU SENS BTU
LDB
LWB
APD
54.3 41.9 60.9 58.7 0.613
54.3 41.9 60.9 58.7 0.613
57.0 45.8 59.1 58.3 0.798

Horizontal Deluxe - High Performance - 600-2200 cfm
Model HDHX
A
B
Filter Size
22
67
63 7/8
(1) 17x52x1


Horizontal Deluxe - High Performance Models 06 thru 12

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 3/4" CW on sizes 15-22 and 1/2" HW on sizes 15-22