DX Horizontal Basic - 200 to 1200 cfm -- Specifications & Dimensions


DX Horizontal Basic - 200 to 1200 cfm -- Specifications & Dimensions

DX COOLING CAPACITIES - ENTERING AIR 80°F DB/67°F WB
SIZE ROWS
CIR.

CFM
08 3 3 975
4 4 925
Suction Temperature 42°
TOTAL BTU SENS BTU
LDB
LWB
APD
30.0 22.1 59.3 57.5 0.587
35.2 24.9 55.4 54.9 0.722
Suction Temperature 45°
TOTAL BTU SENS BTU
LDB
LWB
APD
25.2 20.4 60.9 59.1 0.587
29.8 22.9 57.3 57.0 0.722

Dimensions - Horizontal Basic
Model HBSX
A
B
C
D
E
F
G
08
37 1/2
22 1/4
10 3/8
7 3/16
31
32 7/8
10 5/8

Models 04 thru 12

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 1/2" CW on 04 & 06. 3/4" on 08-12 and 1/2" HW on 04-12.

Coil Company, LLC
3223 Phoenixville Pike
Malvern, PA 19355

800.523.7590 [toll free]
610.251.0257 [local]
610.251.0805 [fax]