DX Horizontal Basic - 200 to 1200 cfm -- Specifications
& Dimensions

|
DX
COOLING CAPACITIES - ENTERING AIR 80°F DB/67°F
WB
|
| SIZE |
ROWS |
CIR. |
CFM |
| 06 |
3 |
3 |
780 |
| 4 |
4 |
710 |
|
|
Suction
Temperature 42°
|
| TOTAL
BTU |
SENS
BTU |
LDB |
LWB |
APD |
| 23.7 |
17.7 |
59.3 |
57.6 |
0.528 |
| 27.0 |
19.1 |
55.4 |
54.9 |
0.608 |
|
|
Suction
Temperature 45°
|
| TOTAL
BTU |
SENS
BTU |
LDB |
LWB |
APD |
| 19.7 |
15.8 |
61.5 |
59.3 |
0.528 |
| 22.6 |
17.6 |
57.3 |
57.1 |
0.606 |
|
|
Dimensions
- Horizontal Basic
|
|
Model
HBSX
|
A
|
B
|
C
|
D
|
E
|
F
|
G
|
|
06
|
37
1/2
|
21
3/4
|
9
|
6
|
31
|
32
7/8
|
9
1/2
|
|
|
Models
04 thru 12
- Right-hand
unit shown, left hand unit opposite.
- Coil
connections determined by facing the supply-air
opening.
- Electrical
junction box is located on the same side as the
coil connections.
- Drain
pan is powder-coated epoxy with 1/4" thick
closed-cell insulation and has 3/4" NPT primary
and secondary drain connections.
- Entire
cabinet, scroll and blower wheel are heavy-gauge,
galvanized steel.
- Coil
connections: 1/2" CW on 04 & 06. 3/4"
on 08-12 and 1/2" HW on 04-12.
|
|
|
 |
 |
 |

| |
Coil Company, LLC
3223 Phoenixville Pike
Malvern, PA 19355 |
800.523.7590 [toll free]
610.251.0257 [local]
610.251.0805 [fax] |
 |
|
|
Home
| Contact
Us | Site
Guide | HVAC
Coils - Replacement or New | Space
Coolers
Quickaire
Fan Coil Units | Stock
Hot Water Booster Coils | Quickaire
Belt Drive Air Handlers | Newsletters
|
|