prod lit
Coil Selection Download
 


Water Horizontal Basic - 200 to 1200 cfm -- Specifications & Dimensions


Water Horizontal Basic - 200 to 1200 cfm -- Specifications & Dimensions

Cooling Capacities for Water Temperature Rise 10° - Entering Air 80° DB/67° WB
SIZE ROWS
CIR.

CFM
08 3 3 975
4 4 925
Entering Water Temperature 42°
TOTAL BTU SEBS BTU GPM WPD APD GPM/CIR. TUBE VEL.
34.5 24.4 7.2 4.9 0.568 2.4 4.1
40.1 27.1 8.4 4.1 0.698 2.1 3.6
Entering Water Temperature 45°
TOTAL BTU SEBS BTU GPM WPD APD GPM/CIR. TUBE VEL.
26.2 21.0 5.5 3.0 0.521 1.8 3.1
30.7 23.5 6.5 2.5 0.652 1.6 2.8

Dimensions - Horizontal Basic
Model HBSW
A
B
C
D
E
F
G
08
37 1/2
22 1/4
10 3/8
7 3/16
31
32 7/8
10 5/8

Models 04 thru 12

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 1/2" CW on 04 & 06. 3/4" on 08-12 and 1/2" HW on 04-12.

Coil Company, LLC
3223 Phoenixville Pike
Malvern, PA 19355

800.523.7590 [toll free]
610.251.0257 [local]
610.251.0805 [fax]