Water Horizontal Basic - 200 to 1200 cfm -- Specifications
& Dimensions
|
Cooling
Capacities for Water Temperature Rise 10° -
Entering Air 80° DB/67° WB
|
| SIZE |
ROWS |
CIR. |
CFM |
| 06 |
3 |
3 |
780 |
| 4 |
4 |
710 |
|
|
Entering
Water Temperature 42°
|
| TOTAL
BTU |
SEBS
BTU |
GPM |
WPD |
APD |
GPM/CIR. |
TUBE
VEL. |
| 27.2 |
19.5 |
5.7 |
2.8 |
0.506 |
1.9 |
3.2 |
| 30.8 |
20.8 |
6.5 |
2.2 |
0.585 |
1.6 |
2.7 |
|
|
Entering
Water Temperature 45°
|
| TOTAL
BTU |
SEBS
BTU |
GPM |
WPD |
APD |
GPM/CIR. |
TUBE
VEL. |
| 20.6 |
16.8 |
4.3 |
2.0 |
0.463 |
1.4 |
2.5 |
| 23.5 |
18.0 |
5.0 |
1.8 |
0.546 |
1.2 |
2.1 |
|
|
Dimensions
- Horizontal Basic
|
|
Model
HBSW
|
A
|
B
|
C
|
D
|
E
|
F
|
G
|
|
06
|
37
1/2
|
21
3/4
|
9
|
6
|
31
|
32
7/8
|
9
1/2
|
|
|
Models
04 thru 12
- Right-hand
unit shown, left hand unit opposite.
- Coil
connections determined by facing the supply-air
opening.
- Electrical
junction box is located on the same side as the
coil connections.
- Drain
pan is powder-coated epoxy with 1/4" thick
closed-cell insulation and has 3/4" NPT primary
and secondary drain connections.
- Entire
cabinet, scroll and blower wheel are heavy-gauge,
galvanized steel.
- Coil
connections: 1/2" CW on 04 & 06. 3/4"
on 08-12 and 1/2" HW on 04-12.
|
|
|
 |
 |
 |

| |
Coil Company, LLC
3223 Phoenixville Pike
Malvern, PA 19355 |
800.523.7590 [toll free]
610.251.0257 [local]
610.251.0805 [fax] |
 |
|
|
Home
| Contact
Us | Site
Guide | HVAC
Coils - Replacement or New | Space
Coolers
Quickaire
Fan Coil Units | Stock
Hot Water Booster Coils | Quickaire
Belt Drive Air Handlers | Newsletters
|
|