DX COOLING CAPACITIES - ENTERING AIR 80°F DB/67°F WB
SIZE ROWS
CIR.

CFM
25 4 26 10000
6 52 10000
8 52 10000
Suction Temperature 42°
TOTAL BTU SENS BTU
GPM

WPD

APD
431.4 290.4 53.4 53.0 0.665
510.3 340.0 48.9 48.9 0.998
594.5 382.4 45.0 45.0 1.331
Suction Temperature 45°
TOTAL BTU SENS BTU
GPM

WPD

APD
375.0 267.5 55.5 55.1 0.665
440.5 313.1 51.4 51.4 0.998
519.6 345.7 48.4 48.4 1.331

Dimensions - Vertical Air Handler 4000 THRU 12000 CFM
Model BVX
A
B
C
D
E
F
G
H J K L M N P Q Filter Size
25
105 1/4
27 1/4
67
24
90
30 1/8
32 1/8
7 5/8 102 7/8 1 1/4 0 107 1/4 19 5/8 1 1/2 1 7/8

(8) 16x20x2
(2) 16x25x2


Model BBVW& BBVX-10 thru 30/ DBVW & DBVX-10 thru 30 (B = Basic, D = Deluxe)

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" to 1" NPT primary and secondary drain connections.