|


 |
 |

DX Vertical - 2 thru 30 tons -- Specifications & Dimensions
|
DX
COOLING CAPACITIES - ENTERING AIR 80°F DB/67°F
WB
|
| SIZE |
ROWS |
CIR. |
CFM |
| 25 |
4 |
26 |
10000 |
| 6 |
52 |
10000 |
| 8 |
52 |
10000 |
|
|
Suction
Temperature 42°
|
| TOTAL
BTU |
SENS
BTU |
GPM |
WPD |
APD |
| 431.4 |
290.4 |
53.4 |
53.0 |
0.665 |
| 510.3 |
340.0 |
48.9 |
48.9 |
0.998 |
| 594.5 |
382.4 |
45.0 |
45.0 |
1.331 |
|
|
Suction
Temperature 45°
|
| TOTAL
BTU |
SENS
BTU |
GPM |
WPD |
APD |
| 375.0 |
267.5 |
55.5 |
55.1 |
0.665 |
| 440.5 |
313.1 |
51.4 |
51.4 |
0.998 |
| 519.6 |
345.7 |
48.4 |
48.4 |
1.331 |
|
|
Dimensions
- Vertical Air Handler 4000 THRU 12000 CFM
|
|
Model
BVX
|
A
|
B
|
C
|
D
|
E
|
F
|
G
|
H |
J |
K |
L |
M |
N |
P |
Q |
Filter
Size |
|
25
|
105
1/4
|
27
1/4
|
67
|
24
|
90
|
30
1/8
|
32
1/8
|
7
5/8 |
102
7/8 |
1
1/4 |
0 |
107
1/4 |
19
5/8 |
1
1/2 |
1
7/8 |
(8)
16x20x2
(2) 16x25x2
|
|
|
Model
BBVW& BBVX-10 thru 30/ DBVW & DBVX-10 thru
30 (B = Basic, D = Deluxe)
- Right-hand
unit shown, left hand unit opposite.
- Coil
connections determined by facing the supply-air
opening.
- Electrical
junction box is located on the same side as the
coil connections.
- Drain
pan is powder-coated epoxy with 1/4" thick
closed-cell insulation and has 3/4" to 1"
NPT primary and secondary drain connections.
|
|
|
 |
 |
 |

Coil Company, LLC
3223 Phoenixville Pike
Malvern, PA 19355
|
800.523.7590 [toll free]
610.251.0257 [local]
610.251.0805 [fax]
|
|
Home
| Contact
Us | Site
Guide | HVAC
Coils - Replacement or New | Space
Coolers
Quickaire
Fan Coil Units | Stock
Hot Water Booster Coils | Quickaire
Belt Drive Air Handlers | Newsletters
|
|