Coil Company HVAC Coils - Replacement or New Contact Us Home
Coil Company
HVAC Coils, Space Coolers, Air Handling Equipment

DX Vertical - 2 thru 30 tons -- Specifications & Dimensions


DX Vertical - 2 thru 30 tons -- Specifications & Dimensions

DX COOLING CAPACITIES - ENTERING AIR 80°F DB/67°F WB
SIZE ROWS
CIR.

CFM
20 4 26 8000
6 39 8000
8 52 8000
Suction Temperature 42°
TOTAL BTU SENS BTU
GPM

WPD

APD
333.7 226.6 54.1 53.6 0.674
409.7 272.0 48.9 48.9 1.011
460.1 294.6 46.3 46.3 1.348
Suction Temperature 45°
TOTAL BTU SENS BTU
GPM

WPD

APD
287.4 208.7 56.1 55.7 0.677
356.0 250.5 51.4 51.4 1.011
401.5 271.4 49.0 49.0 1.348

Dimensions - Vertical Air Handler 4000 THRU 12000 CFM
Model BVX
A
B
C
D
E
F
G
H J K L M N P Q Filter Size
20
85 1/4
27 1/4
67
24
72
30 1/8
32 1/8
6 5/8 76 1/2 1 1/4 0 87 19 5/8 1 1/2 1 7/8 (8) 16x20x2

Model BBVW& BBVX-10 thru 30/ DBVW & DBVX-10 thru 30 (B = Basic, D = Deluxe)

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" to 1" NPT primary and secondary drain connections.