Coil Company HVAC Coils - Replacement or New Contact Us Home
Coil Company
HVAC Coils, Space Coolerts, Air Handling Equipment

DX Vertical - 2 thru 30 tons -- Specifications & Dimensions


DX Vertical - 2 thru 30 tons -- Specifications & Dimensions

DX COOLING CAPACITIES - ENTERING AIR 80°F DB/67°F WB
SIZE ROWS
CIR.

CFM
03 4 7 1200
6 7 1200
8 7 1200
Suction Temperature 42°
TOTAL BTU SENS BTU
GPM

WPD

APD
42.2 30.6 56.7 55.9 0.692
59.0 39.1 50.2 50.2 1.037
69.5 44.2 46.3 46.3 1.383
Suction Temperature 45°
TOTAL BTU SENS BTU
GPM

WPD

APD
35.1 28.2 58.5 58.0 0.674
50.7 36.0 52.6 52.6 1.037
60.6 40.7 49.0 49.0 1.383

Dimensions - Vertical Air Handler 800 THRU 3000 CFM
Model BVX
A
B
C
D
E
F
G
H J K L M N Filter Size
03
30 1/6
27 1/8
46
14
20
17 1/2
20
5 1/32 23 11 1/8 1 32 20 1/8 (1) 20x25x2

Model BBVW& BBVX-02 thru 07.5/ DBVW & DBVX-02 thru 07.5 (B = Basic, D = Deluxe)

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" to 1" NPT primary and secondary drain connections.

  Coil Company, LLC
3223 Phoenixville Pike
Malvern, PA 19355
800.523.7590 [toll free]
610.251.0257 [local]
610.251.0805 [fax]
find us on facebook


Home | Contact Us | Site Guide | HVAC Coils - Replacement or New | Space Coolers