HVAC Coils - Replacement or New Contact Us Home


DX Horizontal - 2 thru 30 tons -- Specifications & Dimensions


DX COOLING CAPACITIES - ENTERING AIR 80°F DB/67°F WB
SIZE ROWS
CIR.

CFM
05 4 8 2000
6 16 2000
8 16 2000
Suction Temperature 42°
TOTAL BTU SENS BTU
GPM

WPD

APD
76.9 53.8 55.4 54.8 0.737
88.4 62.3 51.5 51.5 1.105
108.7 70.8 47.6 47.6 1.474
Suction Temperature 45°
TOTAL BTU SENS BTU
GPM

WPD

APD
65.3 49.6 57.3 56.8 0.737
74.2 54.8 54.9 54.9 1.074
92.8 65.2 50.2 50.2 1.463

Dimensions - Horizontal Air Handler 800 THRU 2000 CFM
Model BHX
A
B
C
D
E
F
G
H J K L M N Filter Size
05
38 1/16
39 1/8
23 11/16
13 13/16
15 15/16
17 1/2
20
11 1/16 29 5/8 7 9/16 1 3/8 36 1/16 40 (1) 16x20x2

Model BBHW& BBHX-02 thru 05/ DBHW & DBHX-02 thru 05 (B = Basic, D = Deluxe)

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" to 1" NPT primary and secondary drain connections.

  Coil Company, LLC
3223 Phoenixville Pike
Malvern, PA 19355
800.523.7590 [toll free]
610.251.0257 [local]
610.251.0805 [fax]
find us on facebook


Home | Contact Us | Site Guide | Quickaire Rooftop Air Handlers | HVAC Coils - Replacement or New | Space Coolers