HVAC Coils - Replacement or New Contact Us Home


Chilled Water Horizontal - 2 thru 30 tons -- Specifications & Dimensions


Cooling Capacities For Water Temperature Rise 10° - 80°F DB/67°F WB
SIZE ROWS
CIR.

CFM
7.5 4 10 3000
6 15 3000
8 15 3000
Entering Water Temperature 45°
TOTAL BTU SENS BTU
GPM

WPD

APD

GPM/CIR.

TUBE VEL.
109.1 79.9 22.9 5.9 0.612 2.3 3.9
133.7 92.2 28.0 4.7 0.931 1.9 3.2
156.5 102.7 33.2 6.5 1.266 2.2 3.8
Entering Water Temperature 50°
TOTAL BTU SENS BTU
GPM

WPD

APD

GPM/CIR.

TUBE VEL.
79.3 68.5 16.8 3.8 0.554 1.7 2.8
97.7 78.2 20.7 3.4 0.859 1.4 2.3
115.6 86.4 24.5 4.3 1.188 1.6 2.8

Model BBHW& BBHX-07.5/ DBHW & DBHX-07.5 (B = Basic, D = Deluxe)

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" to 1" NPT primary and secondary drain connections.