HVAC Coils - Replacement or New Contact Us Home


Chilled Water Horizontal - 2 thru 30 tons -- Specifications & Dimensions


Cooling Capacities For Water Temperature Rise 10° - 80°F DB/67°F WB
SIZE ROWS
CIR.

CFM
30 4 52 12000
6 52 12000
8 52 12000
Entering Water Temperature 45°
TOTAL BTU SENS BTU
GPM

WPD

APD

GPM/CIR.

TUBE VEL.
391.3 300.5 83.0 2.9 0.677 1.6 2.7
528.7 365.1 110.8 4.9 1.058 2.1 3.6
617.7 407.0 129.1 7.9 1.436 2.5 4.2
Entering Water Temperature 50°
TOTAL BTU SENS BTU
GPM

WPD

APD

GPM/CIR.

TUBE VEL.
265.9 265.9 57.3 1.4 0.508 1.1 1.9
387.4 313.0 82.1 3.5 0.976 1.6 2.7
459.1 342.3 97.0 4.6 1.348 1.9 3.2

Dimensions - Horizontal Air Handler 4000 THRU 12000 CFM
Model BHW
A
B
C
D
E
F
G
H J K L M N P Q R Filter Size
30
116 5/16
55 1/4
35 3/16
16 3/16
18 7/8
30 9/16
32 5/16
30 13/16 30 3/4 9 7/16 104 1/2 118 1/2 54 3/4 23 7/8 47 3/4 (8) 16x25x2
(2) 16x25x2

Model BBHW& BBHX-10 thru 30/ DBHW & DBHX-10 thru 30 (B = Basic, D = Deluxe)

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the supply-air opening.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" to 1" NPT primary and secondary drain connections.

Coil Company, LLC
3223 Phoenixville Pike
Malvern, PA 19355
800.523.7590 [toll free]
610.251.0257 [local]
610.251.0805 [fax]

Home | Contact Us | Site Guide |  HVAC Coils - Replacement or New | Space Coolers
Quickaire Fan Coil Units | Stock Hot Water Booster Coils | Quickaire Belt Drive Air Handlers | Newsletters