DX Front / Top Vertical - 400 to 1200 cfm -- Specifications & Dimensions


Cooling Capacities for Water Temperature Rise 10° - Entering Air 80° DB/67° WB
SIZE ROWS
CIR.

CFM
10 3 3 930
4 4 895
Suction Temperature 42°
TOTAL BTU SEBS BTU GPM WPD APD GPM/CIR. TUBE VEL.
36.8 24.9 7.8 8.5 0.437 2.6 4.4
42.5 27.9 9.0 6.9 0.547 2.2 3.8
Suction Temperature 45°
TOTAL BTU SEBS BTU GPM WPD APD GPM/CIR. TUBE VEL.
27.8 21.5 5.8 5.0 0.403 1.9 3.3
32.5 23.8 6.8 4.1 0.513 1.7 2.9

Model BDVW-R
A
B
C
D
E
F
G
FILTER SIZE
10
20 11/32
20 5/16
57 5/8
10 3/8
11 15/16
2 1/8
3 1/16
20x20x1

Cased Vertical with Front Return / Top Supply Models 10 & 12

  • Right-hand unit shown, left hand unit opposite.
  • Coil connections determined by facing the front access panel.
  • Electrical junction box is located on the same side as the coil connections.
  • Drain pan is powder-coated epoxy with 1/4" thick closed-cell insulation and has 3/4" NPT (sizes 10 & 12) primary and secondary drain connections.
  • Entire cabinet, scroll and blower wheel are heavy-gauge, galvanized steel.
  • Coil connections: 1/2" CW on size 10; 3/4" on size 12; 1/2" HW on sizes 10 & 12.

Coil Company, LLC
3223 Phoenixville Pike
Malvern, PA 19355

800.523.7590 [toll free]
610.251.0257 [local]
610.251.0805 [fax]

  

 


Home | Contact Us | Site Guide | Quickaire Rooftop Air Handlers | HVAC Coils - Replacement or New | Space Coolers