Water Front / Top Vertical - 400 to 1200 cfm -- Specifications
& Dimensions

|
Cooling
Capacities for Water Temperature Rise 10° -
Entering Air 80° DB/67° WB
|
| SIZE |
ROWS |
CIR. |
CFM |
| 12 |
3 |
3 |
1135 |
| 4 |
4 |
1075 |
|
|
Entering Water
Temperature 40°
|
| TOTAL
BTU |
SEBS
BTU |
GPM |
WPD |
APD |
GPM/CIR. |
TUBE
VEL. |
| 41.5 |
28.8 |
8.8 |
10.7 |
0.591 |
2.9 |
5.0 |
| 47.8 |
31.9 |
10.0 |
8.4 |
0.722 |
2.5 |
4.2 |
|
|
Entering Water
Temperature 45°
|
| TOTAL
BTU |
SEBS
BTU |
GPM |
WPD |
APD |
GPM/CIR. |
TUBE
VEL. |
| 31.3 |
24.8 |
6.6 |
6.2 |
0.542 |
2.2 |
3.7 |
| 36.7 |
27.6 |
7.7 |
5.2 |
0.675 |
1.9 |
3.3 |
|
|
Model
BDVW-R
|
A
|
B
|
C
|
D
|
E
|
F
|
G
|
FILTER
SIZE
|
|
12
|
20
11/32
|
20
5/16
|
57
5/8
|
10
3/8
|
11
15/16
|
2
1/8
|
3
1/16
|
20x20x1
|
|
|
Cased
Vertical with Front Return / Top Supply Models 10
& 12
- Right-hand
unit shown, left hand unit opposite.
- Coil
connections determined by facing the front access
panel.
- Electrical
junction box is located on the same side as the
coil connections.
- Drain
pan is powder-coated epoxy with 1/4" thick
closed-cell insulation and has 3/4" NPT (sizes
10 & 12) primary and secondary drain connections.
- Entire
cabinet, scroll and blower wheel are heavy-gauge,
galvanized steel.
- Coil
connections: 1/2" CW on size 10; 3/4"
on size 12; 1/2" HW on sizes 10 & 12.
|
|
|
 |
 |
 |

| |
Coil Company, LLC
3223 Phoenixville Pike
Malvern, PA 19355 |
800.523.7590 [toll free]
610.251.0257 [local]
610.251.0805 [fax] |
 |
|
|
Home | Contact
Us | Site Guide
| Quickaire
Rooftop Air Handlers | HVAC
Coils - Replacement or New | Space
Coolers
Quickaire
Fan Coil Units | Stock
Hot Water Booster Coils | Quickaire
Belt Drive Air Handlers | Newsletters
|
|